Softstarter PSTX 55KW 106A 208 - 600VAC (PSTX105-600-70).
Specifications: 1SFA898109R7000 |
||
| Range | Softstarter PSTX | |
| Product ID | 1SFA898109R7000 | |
| Extended Product Type | PSTX105-600-70 | |
| Country of Origin (Estimated) | China (Other) | |
| Warranty | 12 months | |
| CO/CQ | Yes (if need) | |
| Product name & Device short name | PSTX105 | |
| Product specific application | Pumps, fans, compressors and conveyors, Bow thruster, Elevator | |
| Network number of phases | 3 phase | |
| Ue power supply voltage | 208...600 V AC | |
| [Uc] control circuit voltage | 100 ... 250 V AC | |
| Rated Control Circuit Voltage (Uc) | 24 VDC | |
| Rated Operational Power - In-Line Connection (Pe) | (400 V) 55 kW | |
| Rated Operational Current - In-Line Connection (Ie) | 105 A | |
| Communication | Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP | |
| Function available | Built-in bypass for energy saving and fast installation | |
| Overload Protection | Built-in electronic overload protection | |
| Function | Auto phase sequence detection, Automatic restart,,Current limit.Current limit ramp. Dual current limit. Dynamic brake Electricity metering.Electronic overload Time-to-cool Emergency mode Event log Full voltage start Jog with slow speed, forward and reverse Keypad password Kick start Limp mode with two-phase motor control if one set of thyristors is shorted Motor heating Pre-start function Pump cleaning Real time clock Sequence start Soft start with torque control. Soft start with voltage ramp Soft stop with torque control. Soft stop with voltage ramp Stand still brake Start reverse (external contactors) Thyristor runtime measurement Torque limit Voltage sags detection Show less |
|
| Protection Function | Bypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection | |
| Device connection | Both in-line and inside-delta connection | |
| IP degree of protection | IP00 | |
| Dimensions (mm) (H x W x D) |
314x150x198 mm | |
| Net weight (Kg) | 4.6 Kg | |
Contactor thì có khởi động trực tiếp hoặc khởi động sao-tam giác, dưới đây là biểu đồ so sánh khởi động contactor trực tiếp hoặc đấu sao-tam giác với khởi động mềm và bảng so sánh khi dùng các loại như DOL, Y/D, Softstart hoặc Drive:

Khi nào thì chúng ta lựa chọn khởi động mềm PSR, PSE hay PSTX mỗi seri đều có đặc điểm, tính chất khác nhau, tùy vào giá thành, ứng dụng và nhu cầu người sử dụng, chúng ta có bảng lựa chọn dựa trên các đặc điểm kỹ thuật sau:

Tại sao chúng ta sử dụng khởi động mềm vì nó có các tiện ích như giảm được dòng khởi động lên đến 60%, giảm chi phí đầu tư khi làm tủ điện đến 50% và giảm thiểu chi phí bảo trì xuống 40%.