Motor circuit breaker, TeSys Deca, 3P, 0.1 to 0.16A, thermal magnetic, screw clamp terminals, button control.
| Specifications | ||
| Range | TeSys GV2 TeSys Deca |
|
| Country of Origin (Estimated) | Thailand (Other) | |
| Warranty | 12 months | |
| CO/CQ | Yes (if) | |
| Product name & Device short name | GV2ME | |
| Device application | Motor protection | |
| Trip unit technology | Thermal-magnetic | |
| Poles description | 3P | |
| Motor power kW | ||
| Breaking capacity | 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2v |
|
| [Ics] rated service short-circuit breaking capacity | 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| Control type | Push-button | |
| [In] rated current | 0.16 A | |
| Thermal protection adjustment range | 0.1…0.16 A conforming to IEC 60947-4-1 | |
| Magnetic tripping current | 1.5 A | |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Dimensions (mm) (WxHxD) |
45x89x78.5 mm | |
| Net weight (Kg) | 0.26 kg | |